NK8000 Versions, System Limits and Compatibility

NK823x Versions

NK823x Subsystems Compatibility

The following subsystems can be connected to the NK823x Ethernet Port:

NK823x Connectivity Limits

Legacy DMS Connectivity Limits

 

Maximum

NK823x adapter per BACnet network

1

Downstream serial connections per NK823x

4 (note 1)

Subsystems (CC11, CI11, CK11, STT11, STT20, SI400 Sintony, DF8000) per NK823x

50

Subsystems (CC11, CI11, CK11, STT11, FC20, FT20, STT20) per Cerloop via MK7022/NK823x

40

C-Bus stations (CT11, CC11, CI11, CK11) per AlgoRex fire system

16

CK11 gateways per AlgoRex fire system (8 CC11/CI11 panels per CK11)

2

NOTES

  1. Up to 4 downstream connections per NK823x, on the 5 possible communication lines: the 4 COM ports and the I2C line for DF8000. A configuration including all five connections is not supported.

Legacy DMS Connectivity Limits

 

Maximum

Configured objects per NK823x

25,000 (note 1)

NOTES

  1. In DMS configurations, 25,000 configured objects correspond to about 10,000 physical points (detectors, actuators, and so on).

NOTE: After the NK823x unit download, check the connectivity load on your system:

  1. In System Browser, select Management View.
  2. Select the main NK823x node.
  3. In the Extended Operation tab, see the following properties:
    • Last download subsystems count
    • Last download objects count

NK823x Onboard I/O Specifications

3x Digital Inputs:

1x Relay Output:

Unsupported features in NK823x for Desigo CC compared to NK823x for DMS8000