NK8000 Troubleshooting

This section contains NK8000 troubleshooting information.

NK823x Communication Problems

We recommend that you test connections during the configuration process, so you can more easily narrow down the cause of any problems.
This is because you may have problems in runtime where no error message is generated.

The NK823x Ethernet Port generated a fault

The gateway or panel does not respond

Trouble with the serial connection

NK823x malfunctioning with Patrol Agent service

NK823x Configuration Misalignment

When the fire system generates an event, Desigo CC can detect a misalignment with the panel configuration. The source event in Event List helps you to identify the misalignment.

Source Event

Situation

Do the following...

Unidentified

You modified the fire system configuration so that it is no longer aligned with Desigo CC and the NK823x.

Re-import the fire system configuration files into Desigo CC and download the configuration to the NK823x.

Unknown Device

You modified Desigo CC configuration so that it is no longer aligned with the NK823x and the fire system.

NK823x Download Problems

Error Condition

Situation

Do the following...

The firmware download fails to start due to a problem in preparing the firmware files in the NK823x_FW folder.

On a client station, you are downloading a firmware file from a location that is not the shared\firmware\NK823x_FW project folder on the server station.

In this case, the system creates a copy of the new firmware files in the shared\firmware\NK823x_FW folder, from which you will be able to download the firmware again.

If your Windows user account does not have permission to write in this folder, the error occurs.

From the client station, in the security properties of the shared\firmware\NK823x_FW project folder, enable the write permission (or ask your system administrator to do that).

  • Right-click the folder and click Properties
  • Select the Security tab
  • Click Edit
  • Enable the write permission
  • Click OK twice to exit

The configuration download fails to start due to invalid data.

A maximum of 4 downstream connections are supported, including the I2C line. If you configured connections on the 4 COM ports and on the I2C port, the configuration cannot be downloaded.
In the download page, if you try to download an invalid configuration, a dialog box informs you about the problem. From the Extended Operation tab, the download command fails, and an error is logged (see Log Viewer).

Reduce the number of connections and try downloading again.

Firmware version not compatible message in the status bar at the bottom of the screen.

The configuration download fails due to an invalid configuration.

You are trying to download the configuration to an NK823x unit that is not equipped with latest firmware.

Perform the following procedure: Checking and Updating NK823x Firmware and Kernel.

Check Integrity error message in the status bar at the bottom of the screen.

Checksum error in the downloaded file.

The downloaded file is corrupted.

Try to perform the download again. If error persists, contact technical support.